Concrete Q&A: Epoxy-Coated Reinforcement and Cover Depth Against Ground
Author(s):
Publication:
Concrete International
Volume:
40
Issue:
1
Appears on pages(s):
63-64
Keywords:
DOI:
10.14359/51702021
Date:
1/1/2018
Abstract:
Table 20.6.1.3.1 of ACI 318-141 requires that concrete cast against and permanently in contact with ground has 3 in. (76 mm) specified cover over reinforcement. Can this cover be reduced if the reinforcement is epoxy coated?